Single Interlock Preaction System with 502 Deluge Valve Electric Release Trim

Single Interlock Preaction System with 502 Deluge Valve Electric Release Trim

  • UL Logo Mid Grey.jpg
Available Sizes DN50 (2") - DN200 (8")
Approvals UL Listed
Maximum Working Pressure 17.2 bar (250 psi)
System End Connection Flanged (standard) or Grooved (optional)

The Single Interlock Supervised Preaction System is generally used to protect water sensitive areas such as computer rooms, storage areas, libraries, archives, banks, etc., to avoid water damage due to damaged sprinklers or damaged sprinkler piping. Preaction System is also effectively used to have Pre-alarm of a possible fire condition and allows time to extinguish fire by hand held fire extinguishing equipment, prior to water discharge through sprinkler heads. It uses an automatic sprinkler with supplemental detection system. In the event when fire cannot be extinguished by hand held fire extinguishing equipment, the increase in temperature will open one or more sprinkler heads to discharge water.

In normal condition, preaction system does not contain water in the sprinkler piping. The sprinkler piping contains air pressure for the purpose of supervising its leak tightness. As per NFPA, the preaction system employing more than 20 automatic sprinklers is to have the sprinkler piping automatically supervised.

The electric detection system in single interlock preaction system will respond to a fire faster than the automatic sprinkler. When fire is detected through electric system, the primary water control deluge valve opens, allowing water flow into the sprinkler piping in readiness for possible subsequent opening of one or more sprinklers.

Nominal Size  DN 50, 80, 100, 150, 200
Deluge Valve Fig 502 - UL Listed
Check Valve  Model - CH
Sprinkler Alarm UL Listed (optional)
Release Panel UL Listed (optional)
Water Flow Switch UL Listed
Solenoid Valve 24V DC, UL Listed
Automatic Air Supervisor Oil-Less Risermount Compressor (optional)
Air Pressure Maintenance
Device
PMD-1 (optional)
Manual System Shutoff
Valve
UL Listed, Butterfly Valve - Standard supply
(Gate valve optional)
Maximum Working Pressure 17.2 bar (250 psi)
System End Connection Flanged (standard supply)
grooved (optional supply)
 Approval  UL Listed